Abstract
Odor emission from a 6,000 head swine grow-finish facility was measured
in May, 1998. Lagoon odor emission with simulated wind speeds of 2.5 mph
(1.1 m/s) in a new buoyant convective flux chamber ranged from 89 to 123
OU/min-m2 and averaged 100 OU/min-m2. The total odor
emission from the 2.4-acre (9,720 m2) surface-aerated first-stage
lagoon would be 16,163 OU/s at this rate. The aerated lagoon emitted 82%
less odor than similar unaerated lagoons with only half the volumetric
loading rate. Odor emissions from the grow-finish buildings with recirculation
flush pits was18 OU/min-AU. Estimated total farm odor emission of 43 OU/s-AU
was similar to average odor emissions from deep-pit buildings of 36 OU/s-AU
measured in another study.
Introduction and Objectives
Anaerobic lagoons have been used for many years to provide practical
treatment and storage for swine manure, because of their simplicity in
operation and maintenance, and relatively low cost compared to other treatment
methods (Zhang et al., 1996). Lagoons become more odorous when they are
overloaded due to sludge buildups, additional inputs, and cold weather.
Aeration is a well-known method of upgrading existing lagoons to
significantly reduce odor problems, but field data is
lacking.
Submerged static tube aerators (RAMCO
Sales, Inc., Cushing, OK) consist of 4, 8, or 12 inch (10, 20 or 31 cm)
diameter vertical tubes containing 2 or 3 free-turning counter-rotating
turbines that shear a coarse bubble stream of air into fine bubbles. The
aerators are submerged with weights and the air lift action of rising bubbles
keeps the aerator tubes vertical. Coarse air is delivered by air headers
and valved air laterals with a blower providing air at 3 to 7 psi (750
to 1750 Pa) pressure. A short section of flexible hose is connected from
the laterals to the air diffusers which contains several 0.25 or 0.38 inch
(0.7 to 1.0 cm) holes. As this coarse air and water mixture rises, it is
deflected by Venturi rings into the turbines. Because of the large hole
sizes in coarse air diffusers, static tube aeration systems are maintenance-free
(Boss and Aberg, 1987).
A modified static tube aeration system (RAMCO, 1997) was designed to aerate surface water only. A system was installed in the 2.4 acre (9,655 m2) first-stage lagoon at a 6,000-head, swine finishing site in Oklahoma. It began operating on August 8, 1997. The blower provided 33 cfm (56 m3/h) to each of 21 aerators.
The swine finishing site consisted of
six, 31x246 ft (9.45x75m) grow-finish buildings each with four, 10'x125'
(3.1x38.1m) recirculation flush pits (MWPS, 1985). On a weekly basis, the
pits were drained into a first-stage lagoon located about 150 ft (45.7m)
east of the buildings, and recharged with second-stage lagoon water. Slurry
from the second-stage lagoon was used to recharge each pit with about 20
inches (51 cm) of water after flushing the drained pit for 20 minutes.
Each building had a 4 ft (1.2m) thermostatically-controlled curtain on
each sidewall. Sidewall openings were created by lowering these curtains.
There was no ceiling and the ridge had no ventilation openings. The 3 ft
(0.3m) deep flush pits were ventilated via two central underfloor plenums
with 3 in (7.5 cm) diameter holes spaced 10 ft (3.05 m) on center along
the building length on each side. Three, 12" (30 cm) diameter fans exhausted
air from each plenum through a concrete annex located outside each endwall.
The objective of this project was to evaluate odor emissions from the aerated 2.4 acre (9,655 m2) first-stage lagoon and six grow-finish buildings with recirculation flush pits. Another objective was to test the effect of flushing frequency on air quality in the buildings.
Procedure
Ammonia and carbon dioxide concentrations
were measured using a hand-held gas sampling pump and gas absorption tubes.
Replicated samples of CO2 and NH3 were taken at two
locations in each building to assess air quality and gas emissions.
Gas samples from the lagoon and the
buildings were collected in 10 L chemically-inert bags and sent overnight
to Purdue University for analysis by a human panel with dynamic dilution
olfactometry. Dilution thresholds were evaluated by eight panelists.
The heat balance method (Heber et al.,
1998b) was used to estimate airflow rates from each building. Temperatures
in two buildings and the outside temperature were recorded every 20 s using
battery-operated temperature recorders. To
study effects of flushing frequency, building 3 was flushed on May 2 and
building 4 was flushed on May 6. Building emissions measured in buildings
3 and 4 on May 6 and 7 provided a comparison of gas concentrations and
emissions before and after flushing the pit, and after 1, 4, 5 and 7 days
since last flush.
A buoyant convective flux chamber was
designed and constructed for measuring odor emissions from the lagoon surface
under controlled conditions. The chamber covered 8.1 ft2 (0.76
m2) of lagoon surface. Inside chamber walls and ceiling were
lined with stainless steel and surrounded by rigid waterproof insulation
to cause enough buoyance to keep 6 inches (15 cm) of the chamber above
the surface. A buoyant variable air supply unit floating adjacent to the
emission chamber forced air through a gas absorption and dust filtering
system and into the emission chamber through a Teflon hose. Air followed
a hairpin path through the chamber. A surface air velocity of 219 fpm (1.1
m/s) was established by adjusting the variable-speed exhaust fan and measuring
air velocity with a hot-wire anemometer. Samples of air going into and
out of the emission chamber were collected in 2.0-3.0 minutes at an airflow
rate of 0.08 to 0.12 cfm (2.5 to 3.3 Lpm). Odor emission was determined
by multiplying airflow rate through the chamber by the difference between
inlet and outlet odor concentrations.
Lagoon emission was measured on May
4 at five surface air speeds: 20, 41, 176, 268 and 333 fpm (0.10, 0.21,
0.89, 1.36 and 1.69 m/s). The chamber was placed in the lagoon from the
west berm about 170 ft (51.8m) from the northwest corner of the lagoon.
Inlet and outlet odor concentrations were evaluated at each air speed.
On May 5, odor emission was measured twice with inlet and outlet samples
taken both times. On May 6, odor emission was measured with one inlet sample
and three outlet samples. The chamber was placed in the water from the
west berm about 100 ft (30m) from the south end of the lagoon. The same
procedure was used on May 7, but the chamber was placed in the water from
the south berm.
Results and Discussion
Based on a lagoon volume of 575,000
ft3 (16,300 m3) and a surface area of 2.4 acre (9,655
m2), the lagoon was overloaded at the time of testing by 1.5
and 1.8 times based on volume and surface, respectively. The volumetric
volatile solids loading of the first cell was 8.9 lb/1000 ft3
compared to the recommended loading rate of 6 lb/1000 ft3. The
surface loading rate of the lagoon was estimated at 2,131 lb/acre-day as
compared to the 1,200 lb/acre-day maximum recommended by ASAE (1997). The
lagoon had been loaded uniformly for two weeks prior to May 4.
Lagoon slurry temperature was 68F (20C)
as measured by a battery-operated temperature sensor along the edge of
the lagoon. Chemical oxygen demand, biodegradable oxygen demand, total
suspended solids, volatile solids, and dissolved oxygen of samples taken
near the surface of the lagoon were 7,105, 1,646, 1,450, 0.04, and 1,040
mg/L, respectively. Slurry pH was 8.1.
A regression equation was developed
from the May 4 test to determine an odor emission rate of 93 OU/min-m2
at 2.5 mph (1.1 m/s). Odor emission rates on May 5 were 89 and 90 OU/min-m2
for the first and second runs, respectively. Odor emission rates on May
6 and 7 were 123 and 111 OU/min-m2, respectively. Overall, they
ranged from 89 to 123 OU/s and averaged 100 OU/min-m2. The odor
emission rate from the 2.4 acre (9,655 m2) lagoon with a 2.5
mph (1.1 m/s) wind was therefore estimated at 16,163 OU/s.
Odor emissions from unaerated lagoons
at two other swine grow-finish sites were measured in other projects. Lagoons
#1 and #2 had volume loading rates of 5.0 and 3.2 lb VS/1000 ft3-d
and surface loading rates of 988 and 1,926 lb VS/acre-d, respectively.
Odor emissions from lagoons #1 and #2 were 705 and 473 OU/s, respectively,
and averaged 577 OU/s. The aerated lagoon, with twice the volumetric loading
rate, emitted 82% less odor than the unaerated lagoons. This preliminary
data suggested that static tube aeration was very effective in reducing
odor emissions and confirms the findings in the literature concerning the
effectiveness of aeration on odor control.
Buildings 3 and 4 had 1,024 and 925
pigs weighing 120 and 130 lb (55 and 59 kg), respectively. Airflow from
each pit fan was 1,500 cfm (2,550 m3/h) based on a velocity
traverse of the fan air outlets. The three west fans of buildings 3 and
4 were shut off and covered with plastic on May 7 so total pit fan airflow
was reduced from 9,000 to 4,500 cfm (15,300 to 7,650 m3/h).
However, this represented only a small fraction of total ventilation airflow
since curtains were wide open most of the time,. The pit fan plenum was
essentially used as an air sampling duct for evaluating indoor air quality.
The pit fan exhaust air had much higher
ammonia concentration than air exhausted through the curtains. Pit odor
concentration can therefore be assumed to be higher than that of air blowing
crossways through the top part of the building. It was therefore assumed
that average gas concentration of all fan exhaust air was 10% of gas concentration
in the pit fan exhaust air.
Since odor intensity is related to the
log of gas concentration, it was assumed that the average gas concentration
(dilution to threshold) of the overall exhaust stream was 50% of that measured
at the pit fan exhaust. Therefore, total odor emission from the building
was estimated by multiplying odor concentrations at the pit fans by heat
balance airflow and dividing by two. Average odor concentration of air
at the pit fans ranged from 34 to 56 OU. Calculated odor emission rates
were affected by airflow which was much higher on May 7. The airflow rates
of the buildings on May 6 ranged from 58,197 to 69,019 cfm (98,935 to 117,332
m3/h) whereas on May 7, airflow ranged from 327,789 to 377,717
cfm (557,241 to 642,119 m3/h). Odor emissions from buildings
3 and 4 were 595 and 772 OU/s on May 6 and 4,048 and 2,658 OU/s on May
7. The average building odor emission measurement was 2,018 OU/s or 18.3
OU/s-AU. With these assumptions and measurements, total odor emission from
the six grow-finish houses was 12,153 OU/s, as compared to 16,163 OU/s
from the lagoon.
Heber et al. (1998a) reported an average
odor emission rate of 36 OU/s-AU from deep-pit swine grow-finish buildings
based on 80 simultaneous measurements of odor concentration and fan airflow.
The average building odor emission measured in this test with recirculation
flush pits was 18.3 OU/s-AU. The average total farm odor emission was 43
OU/s-AU which was similar to odor emission from deep-pit buildings.
The total odor emission from the farm
was estimated at 28,316 OU/s based on this preliminary set of data. If
the same lagoon was unaerated, it would have generated five times and the
total farm emissions would have been 92,924 OU/s. Using an emission-based
setback model (Williams and Thompson, 1985), it can be calculated that
the aeration system reduced the setback distance for the farm from 0.96
to 0.47 miles (1.54 to 0.75 km).
Uncertainty in odor emission measurements
is due to the following reasons:
Gas measurements showed a slight trend
toward improved air quality in buildings with higher frequency flushing.
There was a large building airflow difference between May 6 and 7 during
odor sampling times. However, odor concentration in the pit exhaust air
was directly proportional to the number of days since last flush. Odor
concentrations were 34, 37, 46 and 56 OU and ammonia concentrations were
7, 8, 9 and 9 ppm for days 1, 4, 5 and 7, respectively.
Paired emission measurements on May
6 representing days 1 and 5 since last flush and May 7 measurements representing
days 4 and 7 were compared with each other since airflows were similar.
Odor concentration, odor emission rate and ammonia concentration of day
5 since last flush were 34, 52, and 34% greater than on day 1, respectively.
Odor concentration, odor emission rate and ammonia concentration of day
7 were 54, 30 and 10% higher than day 4, respectively.
Conclusions
2. Cite as follows: Heber, A.J. 1998. Effect of Lagoon Aeration on Odor Emissions from a Swine Grow-Finish Facility. Final Report to Ramco Sales, Department of Agricultural and Biological Engineering, Purdue University, West Lafayette, IN, September 8.
3. Albert J. Heber, Ph.D., P.E., Associate Professor, Dept. of Agricultural and Biological Engineering, 1146 ABE Building, Purdue University, West Lafayette, IN 47907. Phone: 765-494-1214. Email: heber@ecn.purdue.edu.. URL: http://pasture.ecn.purdue.edu/~heber/